Based on the arsenic TTLC they need to run TCLP and STLC . <br /> The results state "Metals, STLC and the sample prep is "RCRA". RCRA prep should be TCLP results <br /> not STLC. <br /> They need to clarify if STLC or TCLP was done and also do the missing test. <br /> The results reported so far are non haz. <br /> Garrett Backus, Ld. Sr. REHS, CUPA programs <br /> San Joaquin County Environmental Health Department <br /> 1868 E Hazelton Ave, Stockton, CA 95205 <br /> (209)468-2986 gbackus(cbsiaov.org <br /> https://www.smaov.org/department/envhealth/ <br /> SAN JOAQUIN <br /> —QQUKTY— <br /> Gfedmelp 900.1 herr. <br /> From: Keven Jones<kiones(@qualit)zserviceinc.net> <br /> Sent: Wednesday, April 1, 2020 11:44 AM <br /> To: Naidu, Muniappa <Mnaidu(@sjgov.org> <br /> Subject:Arsenic Media Results- Ph. Call 04/01/2020 <br /> Munaippa, <br /> Thanks again for your time today. Just want to confirm that the attached <br /> results, which were sampled from spent arsenic media for a water filtration <br /> system, are non-hazardous. <br /> Give me a call back at (209)322-1192 at your earliest convenience and we <br /> can discuss! Thanks for your help. <br /> Sincerely, <br /> Keven E. Jones <br /> Operations Manager <br /> QUALITY SERVICE, INC. <br /> 1(209)838-7842(Office) <br /> 1(209)322-1192(Direct) <br /> kions qualityserviceinc.net <br />