Laserfiche WebLink
Scope <br /> This procedure will provide a Veeder-Root ATG certified technician a procedure to safely test tank overfill <br /> protection. <br /> Reference Documents <br /> • Veeder- Root TL&3XX Operators Manual (576013- 610) <br /> • Veeder- Root TLS-3XX Setup Manual (576013 -623) <br /> • Veeder- Root TLS-450 Setup and Operation Screens Manual (577013 -940) <br /> • Veeder-Root TLS-450PLUS/TLS4 Operator's Manual (577014 - 110) <br /> • Veeder- Root TLS4 Quick Start (577014 -034) <br /> • Veeder- Root Overfill Alarm Installation Guide (576013-589) <br /> Consoles <br /> i <br /> TLS-450PLUS , TLS4c, TLS4i, TLS450 and TLS3XX <br /> Requirements <br /> TLS -450PLUS , TLS4c , TLS4i, TLS-450 : Automatic Event : Device Task programmed to trigger on Tank Overfill and <br /> t <br /> close a relay feeding voltage to the Overfill alarm device. <br /> TLS-UX : Output relay programmed to close a relay on a Tank Overfill alarm feeding voltage to the Overfill alarm <br /> device. <br /> Testing Procedure <br /> 1 . Inspection <br /> a. Verify the levels in the tank to make sure there is product in the tank and that the tank is enabled. <br /> b. If the site is currently receiving a delivery , wait until the delivery is complete. <br /> c. If the tank is performing a SLD tank test, stop the test. <br /> 2. Preparation <br /> a . Turn Alarm filtering off, as this will allow you to clear alarms quicker. Refer to TLS-3XX Setup manual <br /> (5 7601 3 - 623) or TLS4XX on - line help . <br /> b. Program Delivery delay to 1 minute, this will allow the delivery to be completed quicker. <br /> 1 . Note the customers original value, so you can restore it after the test. <br /> 24 <br />