• <br />Mr. Rod Gonzales <br />April 28, 1989 <br />Page 3 <br />V. Sonora Street Storage Area (continued) <br />I. Tanks shall be supported as to prevent the excessive <br />concentration of loads on the supporting portion of the <br />shell. UFC 79.505(d) <br />J. Tank supports and connections shall be designed to <br />resist damage as a result of earthquake shocks. <br />UFC 79.505(f) <br />K. Steel supports.or pilings for tank shall have a fire <br />resistance rating or.rnot less -than two hours, except <br />solid web steel saddles need not'be protected if less <br />than 12 inches high at their lowest point. <br />UFC 79.505(c) <br />L. Class II or III -A liquids may be dispensed from a <br />container by gravity through a listed self-closing valve <br />or self-closing faucet. UFC 79.806(b) <br />1. Tanks on stilts. <br />M. All weeds, grass, brush, trash or other combustible <br />material shall be kept a minimum of 10 feet away from <br />all LP -gas tanks or containers. UFC 82.109 <br />1. Material stored around tank. <br />VI. Blue Warehouse Storage Area -Exterior <br />A. Keep flammable or combustible liquids in closed <br />containers. UFC 79.102(b) <br />1. Open waste barrels and bucket of combustibles. <br />%JL' <br />B. Defective containers shall be removed from service, <br />repaired or disposed of in an approved manner. <br />UFC 80.301(b)3 <br />1. Several one gallon and five gallon containers of <br />flammable paints and unknown liquids rusted and <br />damaged. <br />C. Exterior storage of corrosive liquids shall not be <br />permitted within 20 feet of any building, an unpierced <br />tw9-hour fire resistive wall not less than 30" above <br />and to the side of the storage area may be provided in <br />lieu of distance. UFC 80.314(x)2 <br />