Laserfiche WebLink
Mr. Rod Gonzales <br />April 28, 1989 <br />Page 4 <br />VI. Blue Warehouse Storage Area -Exterior (continued) <br />D. Secondary containment shall be provided for the storage <br />of corrosive liquids. 80.314(a)5 <br />1. 55-55 gallon barrels hydrochloric acid. muriatic <br />acid, and sodium hydroxide 50% solution. <br />UFC 80.301(L)4. See Appendix "A" <br />E. Segregate incompatible hazardous material storage by a <br />distance of not less than 20 feet or 18" partition above <br />and to side of stored material. UFC 80.301(n) 1,2 <br />1. Distance between combustible liquids and <br />corrosives. <br />F. Class I and 2 water reactive materials shall be limited <br />to piles not greater than 1,000 cubic feet. <br />Aisle widths shall not be less than one half the height <br />of the pile or 10, -feet, whichever is greater. <br />UFC 80.310(b)4 <br />G. Open container of weed killer. UFC 79.102(b) <br />1. Keep away from acids or bases. <br />VII. Equalizer Area <br />A. Keep flammable and combustible liquids in closed <br />containers. UFC 79.102(b) <br />1. Open container oil <br />B. Provide approved safety cans for dispensing flammable <br />liquids. UFC 79.104(a) <br />VIII.Electrical Shop <br />A. Defective container shall be removed from service. <br />1. Rusted unknown container. <br />B. Keep flammable and combustible liquids in closed <br />containers. UFC 79.104(a) <br />1.1\ Open container oil. <br />2. Open container solvent with paper soaking in the <br />container. <br />