Laserfiche WebLink
March 27, 1995 <br />A & S ENGINEERING INC. <br />PLANNING • ENGINEERING • CONSTRUCTION MANAGEMENT <br />45 QUAIL COURT, STE. 303, WALNUT CREEK, CA. 94596 - PHONE: 510-933-0578 - FAX 510.933-0588 <br />San Joaquin County <br />Environmental Health Division <br />445 N. San Joaquin Street <br />Stockton, CA 95201 <br />Attn: Michael Kith <br />MAR 2 a '1995 <br />ENVIRCNMEN?AL HEALTH <br />PERMIT/SERVICES <br />Subj: Shell Station located k@ 2575 Country Club Boulevard, Stockton, CA <br />Dear Mr. Kith, <br />The following items are in response to the information that was requested in your letter dated March 101, <br />1995. <br />ITEM #1 COMMENT: Specify which hydrostatic reservoir sensor (ie. single or <br />dual float) will be used. Provide model number. <br />RESPONSE: The Veeder-Root single float hydrostatic sensor model 07943801-301 <br />will be used. <br />ITEM #2 COMMENT: Specify which sump sensor will be used. (2) sensors are proposed. <br />RESPONSE: _The Veeder-Root piping sump sensor model #794390-205 will be used. <br />ITEM #3 COMMENT: Specify what kind of dispenser sump will be used and how it will be <br />monitored. Submit cut sheets to EHD. <br />RESPONSE: n: e West= fiberglass deep sump dispenser sump model #1642:1:2 XL- <br />rolycon will be used. It will be monitored with visual & audible alai -ins. <br />I'rEm #4 COMMENT: FieK hose served as secondary containment for piping is allowed under <br />dA . enser at the last connection only. <br />RESP I+ IE. Sl2eli Oil will wntain the flex hoses. <br />