Laserfiche WebLink
SWRCB,January 2002 <br /> 7. PIPING SUMP TESTING RE <br /> Test Method Developed By: ❑Sump Manufacturer ❑Industry Standard X Professional Engineer <br /> ❑Other(Spec) 11 2014 <br /> Test Method Used: ❑Pressure ❑Vacuum X <br /> ❑Other(Spec) <br /> Test Equipment Used:Caldwell Level Change Indicator Equipment Re! 37-5 <br /> Sump#1-87 Sump#2-91 Sump#3-Diesel Sump#4-Transition <br /> Sump Diameter: 42" 42" 48" 20" <br /> Sump Depth: 31" 34" 49" 24" <br /> Sump Material: Fiberglass Fiberglass Fiberglass Poly Plastic <br /> Height from Tank Top to Top of 18" 17" 15" 20 ''/z" <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 13" 10 ''/2" 13" 19 ''/z" <br /> Electrical Penetration: <br /> Condition of sump prior to testing: Dry Dry Dry Dry <br /> Portion of Sump Tested' Water Level 20" Water Level 19" Water Level 17" Water Level 23" <br /> Does turbine shut down when <br /> sump sensor detects liquid(both Yes Yes Yes Yes <br /> product and water)?* <br /> Turbine shutdown response time Not Alarmed Not Alarmed Not Alarmed Not Alarmed <br /> Is system programmed for fail-safe Yes Yes Yes Yes <br /> shutdown?* <br /> Was fail-safe verified to be No No No No <br /> operational?* <br /> Wait time between applying water 5 Minutes 5 Minutes 5 Minutes 5 Minutes <br /> and starting test: <br /> Test Start Time: 8:55 9:05 9:45 9:55 <br /> Initial Reading(Rj): .001 .001 .001 .001 <br /> Test End Time: 9:25 9:35 10:15 10:25 <br /> Final Reading(RF): .001 .001 .001 .001 <br /> Test Duration: 30 Minutes 30 Minutes 30 Minutes 30 Minutes <br /> Change in Reading(RF-RI): 0 0 0 0 <br /> Pass/Fail Threshold or Criteria: .005/30 Minutes .005/30 Minutes .005/30Minutes .005/30 Minutes <br /> TestResult:-, Pass Pass Pass Pass <br /> Was sensor removed for testing? Yes Yes Yes Yes <br /> Was sensor properly replaced and Yes Yes Yes Yes <br /> verified functional after testin ? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> ' If the entire depth of the sump is not tested,specify how much was tested. If the answer to gny of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire sump must be tested. (See SWRCB LG-160) <br />