Laserfiche WebLink
SWRCB,January 2002 Page 2 <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: a Tank Manufacturer Industry Standard F] Professional Engineer <br /> El Other (Specify) <br /> Test Method Used: FI Pressure Vacuum ❑ Hydrostatic <br /> ❑ Other (Spec) <br /> Test Equipment Used: Equipment Resolution: <br /> MEMEMINNOMMENESEEM <br /> Em Tank# 1 Tank# 2 Tank# 3 Tank# <br /> Is Tank Exempt From Testing?1 Yes x No Yes x No Yes El No Yes No <br /> Tank Capacity: 10k 10k 10k <br /> Tank Material: dw fiberglass dw fiberglass dw fiberglass <br /> Tank Manufacturer: xerxes xerxes xerxes <br /> Product Stored: reg sup dsl <br /> Wait time between applying <br /> pressure/vacuum/water and 5 min 5 min 5 min <br /> starting test: <br /> Test Start Time: 7:36 7:3 3 7:30 <br /> Initial Reading(Rt): 1011 hg 10"hg 1011 hg <br /> Test End Time: 8:36 8:33 8:30 <br /> Final Reading(RF ): 1011 hg 1011 hg l 0°hg <br /> Test Duration: 1 hr 1 hr 1 hr <br /> Change in Reading(RF-P4 ): 011h 0" hg 0" hg <br /> Pass/Fail Threshold or Criteria: 211 hg 211 hg 211 hg <br /> NINE= NIMBI= <br /> Was sensor removed for testing? YesE]NoDNA Yes x N NA Yes x N NA Yes N NA <br /> Was sensor properly replaced and � � � <br /> verified functional after testing? x Ye N NA x Ye N NA x Ye N NA Ye N NA <br /> Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> 1 Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23,Section 2637(a)(6)1 <br />