Laserfiche WebLink
0 <br />teTffK_TEl( <br />Date: FEB 19, 2010 <br />Location: CRLLC #2705448 <br />3202 W. HAMMER LANE <br />Work Order # 10021901-7 <br />Contact: ARMEN MKRTYTCH/AN <br />STOCKTON, CA 95209 Telephone: (925) 884-0800 <br />SUMP# <br />7-8 <br />7-8 7-8 <br />PRODUCT <br />87 <br />91 DIESEL <br />LD TYPE Mechanical, (W)PLLD, (P)LLD <br />M <br />M M <br />LD MANUFACTURER <br />FE PETRO <br />FE PETRO VMI <br />LD MODEL <br />STP -MLD <br />STP -MLD LD 2000 <br />LD SERIAL NUMBER <br />02071078 <br />02070690 05071049 <br />SUMP CONDITION <br />DRY <br />DRY DRY <br />RESILIENCY <br />165 ML <br />150 ML 100 ML <br />OPERATING PRESSURE <br />28 PSI <br />28 PSI 28 PSI <br />OPENING TIME <br />8 SEC <br />6 SEC 6 SEC <br />METERING PRESSURE <br />10 PSI <br />10 PSI 10 PSI <br />FUNCTIONAL ELEMENT HOLDING PRESSURE <br />18 P.SI <br />18 PSI 18 PSI <br />LEAK RATE LD DETECTED <br />3 GPH <br />3 GPH 3 GPH <br />DOES LD DETECT 3 GPH LEAK RATE? <br />YES <br />YES YES <br />DOES VEEDER-ROOT CONSOLE ALARM? <br />N/A <br />N/A N/A <br />LD PASS OR FAIL? <br />PASS <br />PASS PASS <br />Comments: <br />Technician: RICHARD THOMAS <br />Signature: <br />Contractor Lic. # 803705 <br />TANK-TEK ENVIRONMENTAL CORPORATION <br />607 Elmira Road, PMB 336, Vacaville, CA 95687 — Ph. (707) 446-6151 - Fax (707) 446-6192 - E-mail: tank-tek@cwnet.com <br />31828 Cercle Chambertin, Temecula, CA 92591 — Ph. (951) 699-8058 Fax (951) 699-8059 - E-mail: bballreich@verizon.net <br />