Laserfiche WebLink
i <br /> Responses to uncorrected UST inspection violations for 1810 E Hazelton, <br /> Inspection date: 3/9/2012 <br /> 104. Corrected on site. <br /> 106. Corrected on site <br /> 202. Corrected on site. <br /> 203. Release statement provided, see attachment. <br /> 308 & 308. On March 22, 2012, Fleet Services contacted a licensed,trained, and certified <br /> contractor to inspect and recommend any corrections needed to sump piping slope, <br /> secondary test containment boot disposition, Schrader valve orientation, and release <br /> flows. The contractor confirmed a slope of 1" for the piping, re-oriented the Schrader <br /> valve to point down, and removed the snap taps. Please see attached documentation from <br /> the contractor. <br />