Laserfiche WebLink
Mr. Mich el Kith <br />March 22, 1999 <br />.GROUP INC. Page 2 <br />8. The plan indicates Teleflex flex connector, the cut -sheet shows Hosemaster fles <br />connector. Please specify and submit cut -sheet as needed. <br />See attached Teleflex flex connector cut sheet. <br />�. Overfill containment information and cut -sheet. <br />Overfill containment is OPW 1 C-2100, S gallon spill bucket. See attached cut sheet. <br />00. <br />ut-sheet and third party approval for the proposed flex boots. <br />ee attached Environ flexible entry boot cut sheet. <br />\,11. F3 of the plan does not show striker plate under all tank openings. Please verify. <br />Steel striker plates under each opening. See Section I and details A and B, Sheet F3. <br />12. Dimension and cut -sheet for the dispenser pan. The plan and cut -sheet show different <br />dispenser pans. <br />We propose to use Phil-Tite, FG -4212, dispenser containment. See attached cut sheet. <br />13. The buoyancy calculation is not site specific. The tank size for the calculation on the <br />plan is 12K, in the submittal is 10K. Both calculations do not have engineer stamp and <br />signature. Please submit a site-specific buoyancy calculation with engineer stamp and <br />signature. <br />Site specific buoyancy calculation with engineer stamp and signature is provided. See <br />attached calculations. <br />I trust that these responses satisfactorily address the comments contained in the referenced <br />letter. If you have any questions, feel free to call me. <br />Respectfully, <br />RIJL DESIGN GROUP, INC. <br />4. 4 - <br />Chris Lucia <br />Job Captain <br />F:\PROJECT\CH\96683\DOCS\KITH-CTL.DOC <br />B E L L E V U E, WA LA H A B R A, CA SACRAMENTO, CA S C O T T S D A L E, AZ <br />