Laserfiche WebLink
UNDER DISPEAER CONTAINMENT &C TESTING <br /> Test Method By: O Manufacturer • Industry Standard o Professional Engr o Other(see below) <br /> Test Method Uses: O Pressure O Vacuum • Hydrostatic o Other(see below) <br /> Measuring Equipment Used: INCON TS-STS (Electronic Sump Test System) <br /> Description Disp#9/10 Disp#11/12 <br /> UDC manufacturer Bravo Bravo <br /> UDC material Steel Steel <br /> UDC depth (inches) 9" 9" <br /> Height from UDC bottom to highest Bottom Bottom <br /> piping penetration <br /> Height from UDC bottom to lowest Bottom Bottom <br /> electrical penetration <br /> Condition of UDC prior to testing Dry Dry <br /> Portion of UDC tested Entire Entire <br /> Type of shut-down present Float Float <br /> Was sensor removed for testing? N/A N/A <br /> Was sensor properly replaced after testing? N/A N/A <br /> Depth of water level from UDC bottom (in.) 6" 6" <br /> Wait time for water level to stabilize (hr:min) 0:10 0:10 <br /> Test start time 10:03 AM 10:32 AM <br /> Initial Probe Reading 1.4847 1.6211 <br /> Test end time 10:18 AM 10:47 AM <br /> Final Probe Reading 1.4848 1.6205 <br /> Test duration (hr:min) 0:15 0:15 <br /> Change in water level (t 0.0000 inches) 0.0001 -0.0006 <br /> Pass/Fail threshold (±0.0020 inches/:Hr.) 0.0020 0.0020 <br /> TEST RESULT PASS PASS <br /> Comments: <br /> © 2006 Walton Engineering,Inc. <br />