Laserfiche WebLink
11 <br />SWRCB, January 2002 <br />Page of <br />5. SECONDARY PIPE TESTING <br />Test Method Developed By: <br />X Piping Manufacturer ❑ Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: <br />X Pressure <br />❑ Other (Spec) <br />❑ Vacuum <br />❑ Hydrostatic <br />Test Equipment Used: Pressure Gauges in Psi/Nitrogen <br />iloPiping Run #1 <br />Piping Run #2 <br />Equipment Resolution: 1/10-15 Psi <br />Piping Run #3 Piping Run # <br />Piping Material: <br />Fiberglass <br />Fiberglass <br />Fiberglass <br />Piping Manufacturer: <br />Smith <br />Smith <br />Smith <br />Piping Diameter: <br />3" <br />3" <br />3" <br />Length of Piping Run: <br />Approx. 110' <br />Approx. 90' <br />Approx. 70' <br />Product Stored: <br />Regular 87 <br />Super 91 <br />Diesel <br />Method and location of <br />piping -run isolation: <br />Test boot at STP #1 <br />Test boot at STP #2 <br />Test boot at STP #3 <br />Wait time between applying <br />pressure and starting test: <br />10 Minutes <br />10 Minutes <br />10 Minutes <br />Test Start Time: <br />8:45 <br />8:30 <br />9:00 <br />Initial Reading (RI): <br />3 Psi <br />3 Psi <br />3 Psi <br />Test End Time: <br />9:45 <br />9:30 <br />10:00 <br />Final Reading (RF): <br />3 Psi <br />3 Psi <br />3 Psi <br />Test Duration: <br />1 Hour <br />1 Hour <br />1 Hour <br />Change in Reading (RF -RI): <br />0 Psi <br />0 Psi <br />0 Psi <br />Pass/Fail Threshold or <br />Criteria: <br />No detectable loss <br />No detectable loss <br />No detectable loss <br />Test Result: <br />X Pass 0 Fail <br />X Pass ❑ Fail <br />X Pass 0 Fail Pass Fail <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />