E <br />SWRCB, January 2002 <br />6. PIPING SUMP TESTING <br />C <br />Page of <br />Test Method Developed By: ❑ Sump Manufacturer ❑ Industry Standard X Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: ❑ Pressure ❑ Vacuum X Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: Caldwell Level Change Indicator <br />Sump # 1 Sump # 2 <br />Sump Diameter: 42" 42" <br />Equipment Resolution: .002 <br />Sump # 3 Sump # <br />42" <br />Sump Depth: 601/219 <br />60" <br />60" <br />Sump Material: Fiberglass <br />Fiberglass <br />Fiberglass <br />Height from Tank Top to Top of Product 13" <br />Highest Piping Penetration: Vent 16" <br />Product 14'/2" <br />Vent 18 %2" <br />Product 14" <br />Vent 19" <br />Height from Tank Top to Lowest 1799 <br />Electrical Penetration: <br />18'/2" <br />19" <br />Condition of sump prior to testing: Dry <br />Dry <br />Dry <br />Portion of Sump Tested' Water Line 19" <br />Water Line 21" <br />Water Line 21" <br />Does turbine shut down when <br />sump sensor detects liquid (both X Yes ❑ No ElNA <br />product and water)?. <br />X Yes 11No 11NA <br />X Yes 11No 11NA <br />11Yes 11No ❑ NA <br />Turbine shutdown response time Not Alarmed <br />Not Alarmed <br />Not Alarmed <br />Is system programmed for fail-safe X Yes ❑ No ❑ NA <br />shutdown?` <br />X Yes ❑ No ❑ NA <br />X Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />Was fail-safe verified to be Yes X No ❑ NA <br />o erational?+ <br />Yes X No ❑ NA <br />Yes X No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />Wait time between applying water 5 Minutes <br />and starting test: <br />5 Minutes <br />5 Minutes <br />Test Start Time: 9:15 <br />8:25 <br />8:30 <br />Initial Reading (RI): .001 <br />.001 <br />.001 <br />Test End Time: 9:45 <br />8:55 <br />9:00 <br />Final Reading (RF): .001 <br />.001 <br />.001 <br />Test Duration: 30 Minutes <br />30 Minutes <br />30 Minutes <br />Change in Reading (RF-Ri): 0 <br />0 <br />0 <br />Pass/Fail Threshold or Criteria: .005/30 Minutes <br />.005/30 Minutes <br />.005/30 Minutes <br />Test Result: X Pass ❑ Fail <br />X Pass ❑ Fail <br />X Pass ` ❑ Fail' <br />0 Pass ❑ Fail <br />Was sensor removed for testing? X Yes ❑ No [INA <br />X Yes ❑ No ❑ NA <br />X Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />Was sensor properly replaced and X Yes ❑ No [INA <br />verified functional after testin ? <br />X Yes ❑ No [INA <br />X Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />' If the entire depth of the sump is not tested, specify how much was tested. If the answer to any of the questions indicated with an <br />asterisk (*) is "NO" or "NA", the entire sump must be tested. (See SWRCB LG -160) <br />