Laserfiche WebLink
RliCEIVED <br /> CLC 13 2017 <br /> SWRCB,January 2002 Page of <br /> ENVIRONMENTAL <br /> 4. Cr <br /> .NNWAXNrLAR TESTING <br /> Test Method Developed By: X Tank Manufacturer ❑Industry Standard ❑Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure X Vacuum ❑Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: Gast Vacuum Pump/Vacuum Gauges in Hg. Equipment Resolution: - '/2"x-30"Hg. <br /> Tank#1 Tank#2&3 Tank# Tank# <br /> 777 <br /> No No <br /> 20K 20K Split 10/10 <br /> Glass Steel Glass Steel <br /> Tank Manufacturer: Trusco Trusco <br /> Product Stored: I Regular 87 Super 91/Diesel <br /> Wait time between applying 10 Minutes 10 Minutes <br /> vacuum and starting test: <br /> Test Start Time: 9:50 10:00 <br /> Initial Reading(Ri): -10"Hg. -10"Hg. <br /> Test End Time: 10:50 11:00 <br /> Final Reading(RF): -10"Hg. -10"Hg. <br /> Test Duration: 1 Hour 1 Hour <br /> Change in Reading(RF-RI): 0"Hg. 0"Hg. <br /> Pass/Fail Threshold or Criteria: No loss in Hg. No loss in Hg. <br /> Test Result: Pass Pass <br /> Was sensor removed for testing? Yes Yes <br /> Was sensor properly replaced andL: I I I <br /> verified functional after testi n ? Yes Yes <br /> Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23, Section 2637(a)(6)) <br />