Laserfiche WebLink
METN' <br />Test Method Developed By: <br />El Piping Manufacturer 0 Industry Standard 0 Professional Engineer <br />El Other (Specify) <br />Test Method Used: <br />0 Pressure 0 Vacuum [I Hydrostatic <br />0 Other (Specify) <br />Test Equipment Used: Test reducer boots, Nitrogen and gauges Equipment Resolution: 0.5% of span <br />Piping Run # 87 <br />-Piping Material- <br />Fiberglass <br />-Piping Manufacturer: <br />Smith <br />-Piping Diameter: <br />3" <br />Length of Piping Run: <br />100, <br />Product Stored: <br />Gasoline <br />Method and location of <br />piping -run isolation: <br />Reducer boots/fittings <br />Wait time between applying <br />pressure/vacuum/water and <br />10 minutes <br />starting test: <br />Test Start Time: <br />1:00 pm <br />Initial Reading (Rj): <br />5 psi <br />Test End Time: <br />2:00 pm <br />Final Reading (RF): <br />5 psi <br />Test Duration: <br />1 hour <br />Change in Reading (RF-Rj): <br />None <br />Pass/Fail Threshold or <br />No detectable loss <br />Criteria: <br />Test Result: <br />El Pass 0 Fail <br />Comments — (include information on repairs made prior to testing, and recommendedfollow-up far failed tests) <br />Tightened Clamps in UDC # 7/8, <br />