Laserfiche WebLink
10117MATAU1114MV <br />Test Method Developed By: <br />❑ Piping Manufacturer ®.Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: <br />0 Pressure <br />❑ Other (Specify) <br />❑ Vacuum ❑ Hydrostatic <br />Test Equipment Used: Test reducer boots, Nitrogen and gauges Equipment Resolution: 0,5% of span <br />Piping Material: <br />Piping Ran # 87 <br />Fiberglass <br />Piping Run # 91 <br />Fiberglass <br />Piping Manufacturer: <br />Smith <br />Smith <br />Piping Diameter: <br />3" <br />3" <br />Length of Piping Run: <br />100, <br />100' <br />Product Stored: <br />Gasoline <br />Gasoline <br />Method and location of <br />i in -run isolation: <br />Reducer boots/fittings <br />Reducer boots/fittings <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />10 minutes <br />10 minutes <br />Test Start Time: <br />1:00 pm <br />12:00 pm <br />Initial Reading (R,): <br />5 psi <br />5 psi <br />Test End Time: <br />2:00 pm <br />1:00 pm <br />Final Reading (RF): <br />5 psi <br />5 psi <br />Test Duration: <br />1 hour <br />i hour <br />Change in Reading (RF -RI): <br />None <br />None <br />Pass/Fail Threshold or <br />Criteria: <br />No detectable loss <br />No detectable loss <br />Test Result: ❑ Pass ® Fail 0 Pass d Fail <br />Comments -- (include information on repairs made prior to testing, and recommended follow-upfor failed tests) <br />Possible loose clamps in UDC # 7/8. <br />