Laserfiche WebLink
LG 113 Vendor/Template Page 2 of 3 <br /> Detection time (sec) <1 <1 <1 <br /> Fall time manual reset manual reset manual reset <br /> Precision -standard deviation (in) 0.003474 0.001923 0.005329 <br /> Lower detection limit(in) 0.357 0.321 0.369 <br /> Model E10 Discriminating <br /> Sensor(5 sensing levels) <br /> Detection time (sec) <1 <1 <1 <br /> Fall time manual reset manual reset automatic reset when <br /> water level drops <br /> Precision (in) <br /> Level 1 (low level switch) 0.005 0.002 0.003 <br /> Level 2 0.006 0.002 not evaluated <br /> Level 3 0.004 0.002 not evaluated <br /> Level 4 0.004 0.002 not evaluated <br /> Level 5 (high level switch) 0.004 0.002 0.004 <br /> Lower detection limit(in) <br /> Level 1 (low level switch) 0.536 0.551 0.550 <br /> Level 2 1.266 1.226 not evaluated <br /> Level 3 2.097 2.074 not evaluated <br /> Level 4 2.858 2.895 not evaluated <br /> Level 5 (high level switch) 3.569 3.57 3.596 <br /> Model 510 Discriminating Sensor <br /> Detection time 5-10 min 1-2 hr <1 sec <br /> Fall time (sec) Replaceable Replaceable <1 <br /> Precision - standard deviation (in) <0.0001 <0.0001 0.0045 <br /> Lower detection limit(in) 0.058 0.058 11.566 <br /> Model 516 Discriminating Sensor <br /> Detection time(sec) <1 <1 <1 <br /> Fall time <1 <1 <1 <br /> Precision -standard deviation (in) 0.0038 0.0032 0.0020 <br /> Lower detection limit(in) 0.340 0.369 0.389 <br /> Specificity Results: <br /> Manufacturer and evaluator claim sensors will respond to any liquid. No additional materials tested. <br /> Manufacturer's S 'fications: <br /> Manufacturer states that systems require no calibration. <br /> Annual functional test required. <br /> Model 510 Discriminating Sensor is designed to work with Beaudreau Models 404-4, 500, and 500C Controllers. <br /> Model 516 Discriminating Sensor is designed to work with Beaudreau Models 500, 500C, and 512 Controllers. <br /> Model 516 Discriminating Sensor will not work with Model 404-4 Controller. <br /> Model EOS100 Discriminating Sensor is designed to work with Beaudreau Model 522 Remote Monitoring system i <br /> 522T Monitoring System. <br /> Comments: <br /> Models 404 and 406 Liquid Level Sensors and Models EOS100 and 516 Discriminating Sensors are reusable. <br /> The polymer strip used in Model 510 Discriminating Sensor is designed to be replaceable if desired. <br /> This design allows the end-user to immediately reuse the sensor by replacing the polymer strip, instead of havin( <br /> to 48 hours)for the polymer strip to dry out. <br /> Replacement lowers the risk of false alarms caused by the use of partially dried out polymer strips. <br /> Model 516 Discriminating Sensor is designed to be placed in a sensor well in bottom of a containment sump with <br /> http://www.swrcb.ca.gov/cwphome/ust/leak_prevention/lgl13/Vendor Files/beaudreau elect... 3/28/05 <br />