Laserfiche WebLink
Triangle Environmental, <br />e. <br />'F.E.I. SYSTEMS TANIC, LINE AND LEAK DETECTOR TEST REPORT <br />Facility: QUIKSTOP #00124 <br />Tank #: 1 Work #: 20001055 <br />Product: Unleaded Regular Test Date: 6/10/03 <br />Test Method: System 4000 <br />Capacity: <br />Diameter (in): <br />Product Level (in): <br />Liquid Volume (Gals): <br />Liquid Percent (%): <br />Specific Gravity: <br />Coe£ of Expansion: <br />Water On Tank (in): <br />Water In Tank (in): <br />Test Method: <br />Pump Brand: <br />System Type: <br />Line Pressure (psi): <br />Line Start Time: <br />Line End Time: <br />Line Start Level: <br />Line End Level: <br />Line Test Rate (gph): <br />Line Test Result: <br />TEI LT -3 <br />FE Petro <br />Pressure <br />52 <br />1:00 PM <br />1:15 PM <br />300 <br />300 <br />0.000 <br />PASS <br />