Laserfiche WebLink
TriangleEnvironmental, <br />T.E.I. SYSTEMS TANIC, LINE AND LEAK DETECTOR TEST REPORT <br />Facility: QUIKSTOP #00124 <br />Tank #: 2 <br />Work #: 20001055 <br />Product: Unleaded Plus <br />Test Date: 6/10/03 <br />s <br />Test Method: System 4000 <br />Test Method: <br />R.J. FTA <br />Capacity: <br />Manufacturer: <br />Vaporless <br />Diameter (in): <br />L/D Model: <br />LD2000 <br />Product Level (in): <br />L/D Serial #: <br />01041302 <br />Liquid Volume (Gals): <br />Line Drain Back (ml): <br />50 <br />Liquid Percent (%): <br />I <br />L/D Trip Time (sec): <br />2 <br />Specific Gravity: <br />Holding Pressure (psi): <br />26 <br />Coe£ of Expansion: <br />Metering Pressure (psi): <br />21 <br />Water On Tank (in): <br />L/D Test Rate (gph): <br />3.0 <br />Water In Tank (in): <br />L/D Result: <br />PASS <br />Product Temp. (F): <br />Head Pressure (psi): <br />Test Start Time: <br />Test End Time: <br />Test Method: <br />TEI LT -3 <br />Test Rate (gph): <br />Pump Brand: <br />FE Petro <br />Test Result: <br />System Type: <br />Pressure <br />Line Pressure (psi): <br />52 <br />'�" 1�•,, 4 J� <br />Line Start Time: <br />1:00 PM <br />Test Method: ULLAGE <br />Line End Time: <br />1:15 PM <br />UllageVolume (gals.): <br />! <br />Line Start Level: <br />310 <br />Ullage Test Time: <br />Line End Level: <br />315 <br />Ullage Vacuum (psi): i <br />Line Test Rate (gph): <br />0.005 <br />Ullage Result: N/A <br />Line Test Result: <br />PASS <br />