Laserfiche WebLink
Depth of water level from tank top (inches) <br />Comments: <br />16 <br />17 <br />,. <br />PRODUCT PIPING SUMP TESTING AUG 12 2013 <br />Test Method By: o Manufacturer • Industry Standard o Professional Engr o Other (see below) <br />Test Method Uses: O Pressure O Vacuum • Hydrostatic o Other (see below) <br />Measuring Equipment Used: INCON TS-STS (Electronic Sump Test System) <br />Description <br />Tank #1 <br />Tank #2 <br />Tank #3 <br />10:34 AM <br />Tank product <br />Sump material <br />Gasoline - 89 _ <br />FRP <br />Gasoline - 87 _ <br />FRP <br />Gasoline - 91 <br />FRP <br />4.6447 <br />Test end time <br />Sump diameter (inches) <br />48 <br />48 <br />48 <br />6.4272 <br />3.0338 <br />Sump depth (inches) <br />42 <br />_ <br />41 <br />39 <br />0:15 <br />ion of sump tested <br />Height from tank top to highest <br />piping penetration (inches) <br />14 <br />15 <br />13 <br />Unknown <br />Unknown <br />Height from tank top to lowest <br />electrical penetration (inches) <br />11 <br />10 <br />9 <br />No <br />Was sensor removed for testing? <br />Method of sump attachment to tank <br />Tank Collar <br />Tank Collar <br />Tank Collar <br />Yes <br />Yes <br />Condition of sump prior to testing <br />Dry <br />Dry <br />Dry <br />Port <br />Depth of water level from tank top (inches) <br />Comments: <br />16 <br />17 <br />15 <br />Wait time for water level to stabilize (hrmin) <br />0:10 <br />0:10 <br />0:10 <br />Test start time <br />10:14 AM <br />10:34 AM <br />10:14 AM <br />Initial Probe Reading <br />6.4278 <br />3.0345 <br />4.6447 <br />Test end time <br />10:29 AM <br />10:49 AM <br />10:29 AM <br />Final Probe Reading <br />6.4272 <br />3.0338 <br />4.6443 <br />Test duration (hr:min) <br />0:15 <br />0:15 <br />0:15 <br />ion of sump tested <br />Entire <br />Entire <br />Entire <br />Is system programmed for fail-safe operation? <br />Unknown <br />Unknown <br />Unknown <br />Was fail-safe verified to be operational? <br />No <br />No <br />No <br />Was sensor removed for testing? <br />Yes <br />Yes <br />Yes <br />Was sensor properly replaced after testing? <br />Yes <br />Yes <br />Yes <br />Depth of water level from tank top (inches) <br />Comments: <br />16 <br />17 <br />15 <br />Wait time for water level to stabilize (hrmin) <br />0:10 <br />0:10 <br />0:10 <br />Test start time <br />10:14 AM <br />10:34 AM <br />10:14 AM <br />Initial Probe Reading <br />6.4278 <br />3.0345 <br />4.6447 <br />Test end time <br />10:29 AM <br />10:49 AM <br />10:29 AM <br />Final Probe Reading <br />6.4272 <br />3.0338 <br />4.6443 <br />Test duration (hr:min) <br />0:15 <br />0:15 <br />0:15 <br />Change in water level (t 0.0000 inches) <br />-0.0006 <br />-0.0007 <br />-0.0004 <br />Pass/Fail threshold (10.002 inches / } Hr.) <br />0.0020 <br />0.0020 <br />0.0020 <br />TEST RESULT <br />PASS <br />PASS <br />PASS <br />wig vvaiwn oiyuiccnny, uH:. <br />