Laserfiche WebLink
Jan. 19. 2009 1 : 09PM West Star Environmental, Inc. No- 7703 P. 3/7 <br /> u n rs�U,i nuua:y /-vv/- Page 2 of <br /> 4. TANK ANNULAR TESTING <br /> Test Method]Developed By: Tank Manufacturer Ina Standard Professional Engineer <br /> Otber(Specify) CS B <br /> Test Method Used: Pressure Vacuum Hydrostatic <br /> other(Specify) X <br /> Test Equipment Used! INCON STS Equipment Resolution: _002 <br /> Tank# Tank # Tank# Tank# <br /> Is Tank Exempt From Testing? Yes Yes No Yes No Yes No <br /> Tank Capacity: 13,000/7,000 <br /> Tank Material: FEBERGLASS <br /> Tank Manufacturer: J00R. <br /> Product Stored: GASOLENE <br /> Wait time between applying <br /> pr uum/water and <br /> starting test: 20N41N <br /> Test Start Time: 10:00am <br /> initial Reading(Rl): 10VAC <br /> Test End Time: 11.00 <br /> Final Reading(RF): IOVAC <br /> Test Duration: IHR <br /> Change in Reading(RF-RI): OVAC <br /> Pass/Fail Threshold or Criteria: NONE NONE NONE NONE <br /> Test Result: (-Pass-) Fal! Pass Fall Pass Fail paw Fall <br /> Was sensor removed for testing? No A FYes o N/A Yes o N/A Yes o N/A <br /> Was sensor replaced an <br /> verified functional No N/A testing? Yes No N/A Yes No N/A Yes No N/A <br /> Comments-(include information on repairs made prior io testing, and recommended follow-up for failed tests) <br /> Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing.-California Code of Regulations,Title 23,Section 2637(ax6)) <br />