v® <br /> Co nits must have EYS seal fittings <br /> sump/dispenser pan and cover a;, °'. Warning installed in accordance with NFPA <br /> Weatherproof 70 (National Electric Code) and NFPA <br /> /junction box 30A(Automotive and Marine Service <br /> Station Code). Failure to seal conduits <br /> in accordance with NFPA 30A, and <br /> NFPA 70 could allow flammable vapors <br /> eys(epoxy- to travel through the conduit in the <br /> filled)yseal p <br /> 1/2 or 3/4 inch ATG COnSOIe.An explosion could <br /> rigid metal fitting <br /> conduit result causing serious injury, property <br /> to ATG loss, or death. <br /> console <br /> TSP-uLS You must install a weatherproof, electrical junction <br /> box inside each manhole. The junction box should be <br /> installed high on the manhole wall to prevent it from being <br /> submerged during heavy rains. <br /> Figure 3:Installation in Sumps/Dispenser Pans <br /> Seal all threaded fittings and conduit <br /> 6. Power up Console for next step. Caution threads to produce a weatherproof seal <br /> 7. Test sensor(verify that an alarm is produced at ATG during installation/maintenance. <br /> console), if it does produce an alarm, seal EYS seal Electrical Wiring <br /> fittings and electrical connectors with epoxy. <br /> 8. Turn off power again if other devices are to be <br /> installed (Repeat Step 3). 1-1WR(RED)P <br /> 9. Reinstall all safety covers and guards,junction ® N(WHT) IN <br /> box gasket and covers—use pipe-dope to seal all ® GND(aLK, (WHT) GND <br /> ® PWR(RED) (BILK)fitting threads. <br /> GND BLK <br /> 10. Install the manhole cover. 2 wires/cable from console <br /> 11. Record the location where the sensor was 2-conductor cable from sensor <br /> installed on the chart on the last page of these <br /> instructions. This information will be needed when <br /> .1-box Insert the unstripped wires fully <br /> programming the ATG. IMIinto the self-sealing,no-strip <br /> 12. Turn on power and program the ATG—Ref: all electrical connector. <br /> relating to Sensors in the Setup/Programming Note: The Use slip-joint pliers and seat <br /> PWR(red) , the black portion to make a <br /> Guide manual. terminal is good electrical connection <br /> not used with <br /> General Installation Notes 2-wire sensors <br /> * Steel double-walled tanks are equipped with a pipe From 2-wire sensor <br /> that allows direct access to the bottom of the interstitial <br /> (annular) space. When installing a riser pipe in a steel Figure 4: TSP-ULS Wiring <br /> tank, codes may require a non-conductive isolation Reference the ATG Installation Manual and see Figure 4 <br /> bushing be installed between the tank and riser pipe. (above)for TSP-IJ LS sensor wiring details.The two-wire <br /> Warning it is the installer's responsibility to TSP-ULS sensor does not have a red (power)conductor, <br /> comply with all applicable federal,state therefore, the PWR (RED) interface terminal at the console <br /> and local codes. Failure to do so may is not used. When a 3-conductor Alpha cable is used, the <br /> create an Environmental Hazard. red conductor can be clipped or taped back on both ends. <br /> * Fill the bottom of the manhole with crushed stone to <br /> facilitate drainage when the TSP-ULS is installed in the Testing the TSP-u LS <br /> interstitial space of a steel tank. Do not cover the top of the Testing this device is a matter of rotating the sensor 180 <br /> riser with fill material, it must remain accessible for service degrees with the bottom up, to cause an alarm at the ATG <br /> and for sensor installation. console. Test the sensor for proper operation on a yearly <br /> Plan your conduit routing. Dig trenches as necessary to basis, or more frequently per local code. <br /> install rigid threaded conduit (RMC)from each manhole <br /> junction box to the Intrinsically Safe (I.S.) knockouts at the <br /> ATG console. The conduit may enter the manhole either <br /> from its bottom or through its side.A junction box inside <br /> of the building as a pull box to combine several sensor <br /> cables. If this is done, then only one I.S. conduit knockout <br /> will be used. <br /> 3 <br />