Laserfiche WebLink
Primary Piping System Installation <br /> JOINT PREP ADHESIVES <br /> Cleaning the Bonding Surfaces Several basic adhesive systems are available from FGS <br /> It is recommended that all bonding surfaces be Smith Fibercast. The 7000 and 8000 series adhesives differ <br /> cleaned before bonding. DO NOT TOUCH THE BONDING in operating characteristics and working time(pot life). See <br /> SURFACES OR ALLOW THEM TO BECOME CONTA. Table 6 for recommended usage and approximate number <br /> MINATED. of bonds per kit. The working life of each kit is based on an <br /> ambient temperature of 75°F(24°C). <br /> Acceptable cleaning methods are as follows: <br /> • Sand all bonding surfaces until contamination is The adhesives are a two-component system that must <br /> removed. However,the sanding operation must be light be mixed prior to use. Detailed instructions for adhesives are <br /> enough to prevent changing the taper angle. provided with each kit. Read these instructions thoroughly <br /> • Cut off contaminated surfacea r p ce with ne and follow the recommended procedures. The cure time and <br /> taper or sleeve coupling. pot life of the adhesive is dependent on temperature. Refer <br /> • Wire brushes may be used to the adhesive instructions. Ambient temperatures above <br /> for cleaning T.A.B. surfaces; 100°F require extra care by the fabricator to assure sufficient <br /> however, they must be clean working time of the adhesive. Refer to Adhesive Working <br /> and free of oil contamination. Life(page 7)for both warm and cool weather conditions. <br /> • Dirt contamination can be <br /> removed by water washing. 1�6ADHESIVE MIXING " <br /> NOTE: Using solvent as a cleaning method is optional. <br /> Solvent may be used if preferred by the customer. Some a <br /> alternate cleaning solvents available through local hardware <br /> or industrial supply houses are acetone,methylene chloride, <br /> and methyl ethyl ketone. After cleaning,be sure any residual <br /> solvent has evaporated before applying adhesive. DO NOT <br /> USE SOLVENTS THAT LEAVE AN OILY FILM ON THE <br /> BONDING SURFACES. <br /> WARNING: Some degreasers and solvents are <br /> extremely flammable. Be sure to read warning Thoroughly mix the adhesive. Complete information and <br /> labels on containers. Never use gasoline, safety precautions are packaged with each adhesive kit. <br /> turpentine, or diesel fuel to clean joints. Be sure all solvent Review all safety precautions thoroughly before mixing <br /> has evaporated before applying adhesive. the adhesive. <br /> Repairing Weathered Surfaces (UV Degradation) • At 65°F or below, prewarm the <br /> When machined surfaces of pipe and fittings are exposed adhesive kits to 70° to 80°F ardeyW <br /> to direct sunlight for a prolonged period of time, the result minimum. <br /> could be a loss of bond strength. All machined surfaces that • Empty all of the contents of the <br /> have turned yellow or brown in color must be repaired. For <br /> hardener bottle into the can of base Adhesive <br /> exposed T.A.B. ends, cut 1/2" minimum off of the end of the adhesive. <br /> spigot and retaper. Exposed fitting bells and pipe tapers • Mix all of the adhesive with all of <br /> should be lightly sanded with an 80 to 120 grit sandpaper the hardener. NEVER SPLITAKIT. <br /> or Emery cloth until the original factory-fresh appearance • Do not spill hardener during the mixing process. Cut <br /> returns. T.A.B. couplings cannot be repaired; they must be through the adhesive with the edge of the mixing stick to <br /> replaced. assist in mixing the two components. <br /> • Mix until the adhesive has a uniform color and a <br /> consistent flow off the mixing stick. Wipe down the <br /> sides, bottom, and under the rim of the can with the <br /> mixing stick to assure complete mixture. <br /> 6 <br />