Laserfiche WebLink
.: <br /> m JIM <br /> NNUL <br /> C <br /> Test Method By. • Manufacturer © ndusffy$tandard .O PrafesslonalEngr 0.0ther,(sea`below) <br /> Test Method Uses. o pressure ' Vacuum o Hydrostatic' o Qtht3r{see below) <br /> Measurin `ui tment Used: Vacuum Ge au <br /> g E q p g '_(range 0 to 30 inches`Hg) <br /> ®escri tion Tat11C#7 Tantc#2 Tan 1C#3 <br /> Product stored Gasoline-87 Gasoline-91 Diesel <br /> Tank manufacturer Modern Modern Modern <br /> Tank material Steel Steel Steel <br /> Tank capacity (US gallons) 8,000 4,000 12,000 <br /> Is this a multi-compartment tank? Yes Yes 1 No <br /> Dry or Brine filled annular? Dry N/A Dry <br /> Monitoring system show normal annular? Yes Yes <br /> Is water table above tank bottom? Unknown Unknown <br /> Was sensor removed for testing? Yes Yes <br /> Was sensor properly replaced after testing? Yes Yes <br /> Veit time for vacuum to stabilize (hrmin) :20 :20 <br /> Test start time 10:53 AM 10:43 AM <br /> Initial vacuum (inches Hg) 7.0 7.0 <br /> Test end time 11:53 AM 11:43 AM <br /> Final vacuum (inches Hg) 7.0 7.0 <br /> Test duration (hr:min) 1:00 1:00 <br /> Change in vacuum (inches Hg) 0.00.0 <br /> Pass/Fall threshold (inches lig!hour) 2.0 2.0 <br /> TEST RESULT PASS PASS <br /> Comments: <br /> 4?2015 Walton Engineering,Inc. <br />