Laserfiche WebLink
DE <br /> I T I <br /> sst Method By: . : :: o Mar u€acturer' Q 1 duetry Stantfard O Professional Engr.:0 Other(see belaW)` <br /> Test Method USES. O Pressure 0 Vacuum ro Oyer Sa below} <br /> Measuring Equipment Used. 1NCON TS-STS :{Electronic Sump Test system} <br /> Desai tion Dis ., 912 Dts #3/4 ;`Dts 5/& bis #718 <br /> UDC manufacturer Total Containment Total Containment Total Containment Total Containment <br /> UDC material Poly "PolyPoly Poly <br /> _UDC depth (inches) 38 38 38 38 <br /> Height from UDC bottom to highest 6 10 14 13 <br /> piping penetration <br /> Height from UDC bottom to lowest 10 6 10 10 <br /> electrical penetration <br /> Condition of UDC prior to testing Dry Dry Dry Dry <br /> Portion of UDC tested Entire Entire Entire Entire <br /> Type of shut-down present Sensor Sensor ' Sensor Sensor <br /> Was sensor removed for testing? Yes Yes Yes Yes <br /> Was sensor properly replaced after testing? YesYes Yes Yes <br /> Depth of water level from UDC bottom (in.) 12 16 15 <br /> Wait time for water level to stabilize (hr:min) :10 :10 :10 <br /> Test start time 1:19 PM 1:19 PM 2:11 PM <br /> Initial Probe Reading 5.0196 2.7222 1.3179 <br /> Test end time 1:35 PM 1:35 PM 2:26 PM <br /> Final Probe Reading _ 4.9760 2.72331.3178 <br /> Test duration (hrmin) 0:16 0:16 O:iS <br /> Change in water level (it 0.0000 inches) -0.04360.0011 -0.0001 <br /> Pass/Fail threshold (±0.002 Inches/ Hr.) 0.00200.0020 0.0020 <br /> N 0 <br /> TEST RESULT FAIL PASS PASS <br /> Comments: <br /> 0 2015 Walton Engineering,Inc. <br />