Test i;4ti1C�t i Manufacturer o IndustryStandard Professional ngr. O Other:{see below) <br />TeS� Ni@tiOC� USQS: C7 Pressure • Vacuum ,0 Hydrostatic Q O er (see below) <br />.......... <br />eaSUrillg EtUlptllent Used:: Vacuum Gauge (range0 io 3t1 inches Hgj <br />®escriaytrn Tank1 Tank >#2 Tank #3 <br />Tank Manufacturer <br />Joor <br />Joor <br />Joor <br />Tank Type <br />Steel <br />Steel <br />Steel <br />Tank Capacity <br />10,000 <br />4,000 <br />6,000 <br />Product Stored <br />Gasoline - 87 <br />Gasoline - 91 <br />Diesel <br />Is this a multi compartment tank?Yes <br />Yes <br />Yes <br />Brine filled or Dry Annular? <br />Dry <br />N/A <br />N/A <br />(if brine filled, perform no vacuum testing) <br />Monitoring system show normal annular? <br />Yes <br />N/A <br />N/A <br />Is water table above tank bottom? <br />Unknown <br />N/A <br />N/A <br />Was sensor removed for testing? <br />Yes <br />N/A <br />N/A <br />Was sensor properly replaced after testing? <br />Yes <br />N/A <br />N/A <br />Waft time for vacuum to stabilize (hr:min) <br />0:10 <br />Test starttime <br />8:20 AM <br />Initial vacuum (inches Hg) <br />7 <br />Test end time <br />10:20 AM <br />Final vacuum (inches Hg) <br />7 <br />Test duration (hours:minutes) <br />2:00 <br />Change in vacuum (inches Hg) <br />0 <br />Pass/Fail threshold (inches Hg/hour) <br />2 <br />TEST RESULT <br />PASS <br />Comments: <br />Tank #2 is the second compartment of a three compartment tank (#1 /#2/#3). <br />No annular testing performed. <br />Tank #3 is the third compartment <br />of a three compartment <br />tank <br />(#1/#2/#3). <br />No annular testing performed. <br />0 2002 Walton Engineering, Inc. <br />