Laserfiche WebLink
11 <br />SWRCB, January 2002 Page of <br />t Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br />containment, such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment <br />4. TANK ANNULAR TESTING <br />Test Method Developed By: <br />0 Tank Manufacturer X Industry Standard- NFPA 30 <br />0 Other (Spec) <br />0 Professional Engineer <br />Test Method Used: <br />0 Pressure X Vacuum <br />X Other (Specify) or acoustical mic UST 2001 <br />0 Hydrostatic <br />Test Equipment Used: UST 2001 or Mc Daniels / 3D test gauges — NIST <br />EEEENMNEN� <br />Tank # 1 Tank # <br />Equipment Resolution: +/- 0.25% fs <br />EM <br />Tank # Tank # <br />Is Tank Exempt From Testing?' <br />X No 0 Yes 0 No <br />0 Yes 0 No <br />0 Yes 0 No <br />Tank Capacity: <br />15000 <br />Tank Material: <br />Steel <br />Tank Manufacturer: <br />Trusco <br />Product Stored: <br />Jet fuel <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />Test Start Time: <br />9am <br />Initial Reading (Ri): <br />6.6" Hg <br />Test End Time: <br />10:50 am <br />Final Reading (RF): <br />6.6" Hg <br />Test Duration: <br />1 hour 50 min <br />Change in Reading (RF -RI): <br />0.0 <br />Pass/Fail Threshold or Criteria: <br />Test Result: <br />X Pass 0 Pass 0 Fail <br />0 Pass 0 Fail <br />® Pass 0 Fail <br />Was sensor removed for testing? <br />X Yes 0 No 0 NA 0 Yes 0 No 0 NA <br />0 Yes 0 No 0 NA <br />0 Yes 0 No 0 NA <br />Was sensor properly replaced and <br />verified functional after testin ? <br />XYes 0 No 0 NA 0 Yes 0 No 0 NA <br />0 Yes 0 No 0 NA <br />0 Yes 0 No 0 NA <br />Comments — (include information on repairs made prior to testing, and recommended follow-up or ailed tests) <br />t Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br />containment, such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment <br />