SWRCB,January 2002 Page 5. <br /> 7. UNDER-DISPENSER CONTAINMENT (UDC)TESTING <br /> Test Method Developed By: UDC Manufacturer �X Industry Standard ❑ Professional Engineer <br /> Other (Sped) <br /> Test Method Used: F] Pressure Vacuum Hydrostatic <br /> ❑ Other (Specify) <br /> Test Equipment Used: incon Equipment Resolution: +- .0020 <br /> UDC# 1-2 UDC# 1-2 UDC# 3-4 UDC# 3-4 <br /> UDC Manufacturer: f iberg f iberg f iberg f iberg <br /> UDC Material: f iberg f iberg f iberg f iberg <br /> UDC Depth: 24" 2 4" 2411 2411 <br /> Height from UDC Top to Top of 10" l0" 1011 l0" <br /> Highest Piping Pentration: <br /> Height from UDCTop to Lowest 411 411 411 411 <br /> Electrical Pentration: <br /> Condition of UDC prior to testing: clean clean clean clean <br /> Portion of UDC Tested: 1 2"above 2"above 2"above 2 11 above <br /> Does turbine shut down when <br /> sump sensor detects liquid(both ❑Yes EIN�N ❑Yes�N�N ❑Yes❑N�N Yes❑NoXINA <br /> product and water)?* <br /> Turbine shutdown response time: <br /> Is system programmed for fail-safe ❑ ❑ ❑ ❑ ❑ F <br /> ❑ <br /> shutdown?* Yes N X N ❑Yes N X N Yes N X N Yes No X <br /> Was fail-safe verified to be ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ <br /> operational?* Yes N X N Yes N X N Yes N X N Yes No X <br /> Wait time between applying <br /> pressure/vacuum/water and starting 15min 15min 15min 15min <br /> test: <br /> Test Start Time: 1 142 158 142 158 <br /> Initial Reading(RI 1 4.6375 4.6483 3.8828 3 .8775 <br /> Test End Time: 157 213 157 215 <br /> Final Reading(RF): 4.6483 4.6470 3 .8839 3 .8774 <br /> Test Duration: 15min 15min 15min 15min <br /> Change in Reading(R F-Ri ): +.0008 - .0012 +.0011 -.0001 <br /> Pass/Fail Threshold or Criteria: .0020 .0020 .0020 .0020 <br /> Wil <br /> SOMME= <br /> Was sensor removed for testing? X Yes❑NoONA MZ[:]No❑NA E]Yes❑N NA Yes[]No <br /> Was sensor properly replaced and r—__1 oYesaN�NA �Yes]Nc❑NA Yes�No�T <br /> verified functional after testing? <br /> Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> 1 If the entire depth of the UDC is not tested,specify how much was tested.If the answer to-any-of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br />