Laserfiche WebLink
SWRCB,January 2002 Page 1 of 1 <br /> 9. SPILL/OVERFILL CONTAINMENT BOXES <br /> Facility is Not Equipped With Spill/Overfill Containment Boxes r <br /> Spill/Overfill Containment Boxes are Present,but were Not Tested <br /> Test Method Developed By: ®' Spill Bucket Manufacturer W Industry Standard r Professional Engineer <br /> Other(Specify): <br /> Test Method Used By: r Pressure P7 Vacuum r Hydrostatic <br /> Other(Specify): <br /> Test Equipment Used:VACUUM TEST Equipment Resolution:0.1 gph <br /> spill Taxi TI 1pill B T�ttk T2 <br /> S[JPREI - 1- RIi LT11iLEAIb m I„X11- spill Bax#€ Spill Bct # <br /> Bucket Diameter: 12.00 12.00 <br /> Bucket Depth: 13.00 13.00 <br /> Wait time between applying <br /> pressure/vacuum/water and 5 min 5 min min min <br /> starting test <br /> Test Start Time: 09:28:00 09:34:00 <br /> Initial Reading(Rj): 30.00 in.H2O 30.00 in.H2O <br /> Test End Time: 09:29:00 09:35:00 <br /> Final Reading(RF): 28.00 in.H2O 29.00 in.H2O <br /> Test Duration: 1 min I min <br /> Change in Reading(RF-Rj): -2.00 in.H2O -1.00 in.H2O <br /> Pass/Fail Threshold or Criteria: +/-4.00 +/-4.00 +/- +/- <br /> Test Resailt 1?asp Puss <br /> Comments-(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> , .. <br /> WO:2314890 <br />