Laserfiche WebLink
e <br /> Page 2 of 7 <br /> 1. TANK ANNULAR TESTING <br /> Test Method Developed By: ❑Tank Manufacturer ®Industry Standard ❑Professional Engineer <br /> []Other(Specify) <br /> Test Method Used: ❑Pressure ®Vacuum ❑Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: See attached testing procedures Equipment Resolution: <br /> Tank <br /> #87 Tank# 91 Tank# Tank# <br /> P1sTank Exempt From Testing?' ❑Yes ®No ❑Yes ®No ❑Yes ❑No ❑Yes ❑No <br /> Tank Capacity: <br /> Tank Material: . Fiberglass Fiberglass <br /> Tank Manufacturer: <br /> Product Stored: Regular(87) Premium(91) <br /> Wait time between applying <br /> pressure/vacuum/water and 15 minutes 15 minutes <br /> starting test: <br /> Test Start Time: 8:38am 8:04am <br /> Initial Reading(Rj): 10"HG 10"HG <br /> Test End Time: 9:38am 9:04am <br /> Final Reading(RF): 10"HG 10"HG <br /> Test Duration: 1 hour 1 hour <br /> Change in Reading(RF-Rj): 0 0 <br /> Pass/Fail Threshold or Criteria: 0.00 0.00 0.00 0.00 <br /> Was sensor removed for testing? ❑Yes®No®NA ❑Yes®No❑NA ❑Yes❑No❑NA ❑Yes®No[]NA <br /> Was sensor properly replaced and ❑Yes❑No®NA ❑Yes❑No®NA ®Yes®No❑NA ❑yes❑No❑NA <br /> verified functional after testing? <br /> Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23,Section 2637(a)(6)) <br />