Laserfiche WebLink
Page 7 of 7 <br /> 9. SPILL/OVERFILL CONTAINMENT BOXES <br /> Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ <br /> Spill/Overfill Containment Boxes are Present,but were Not Tested ❑ <br /> Test Method Developed By: ❑ Spill Bucket Manufacturer ®Industry Standard ❑Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑Pressure ❑Vacuum ❑Hydrostatic <br /> ®Other(Spec) I hour visual leak test <br /> Test Equipment Used: See attached testing procedures Equipment Resolution: <br /> Spill Box# 87 fill Spill Box# 91 fill Spill Box#87 vapor Spill Box#91 vapor <br /> Bucket Diameter&Brand: 12" 12" 12" 12" <br /> Bucket Depth: 14.5" 14.5" 15.5" 15.5" <br /> Wait time between applying <br /> pressure/vacuum/water and 30 Minutes 30 Minutes 30 Minutes 30 Minutes <br /> starting test: <br /> Test Start Time: 8:24am 8:24am 8:24am 8:24am <br /> Initial Reading(Rj): 9 3/4" 9 5/8" 10 5/8" 10 3/8" <br /> Test End Time: 9:24am 9:24am 9:24am 9:24am <br /> Final Reading(RF): 93/491 9 5/8" 10 5/8" 10 3/8" <br /> Test Duration: 1 hour 1 hour 1 hour 1 hour <br /> Change in Reading(RF-RI): 0 0 0 0 <br /> Pass/Fail Threshold or 0.002 0.002 0.002 0.002 <br /> Criteria: <br /> All <br /> Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> Heavy winds & rain— 1 hr visual leak test <br />