Laserfiche WebLink
Performance specifications listed below represent values <br />that could be expected from a TLS -250 if a perfectly <br />cylindrical, calibrated (10 -foot diameter, 10,000 -gallon) <br />tank was used. <br />Height of Fuel at location <br />of DSP - 0.1 inch <br />Volume of Fuel - 15 gallons <br />Leak Detection Mode - 0.1 gallon <br />Fuel Temperature <br />Time <br />- 1 1/2 degrees F <br />- Minutes/Week <br />When the RS -2320 Serial Interface Communications Port is <br />used, each site location can be queried for a system status <br />report. This report checks the system's operational status <br />by transmitting the data, time, whether the leak monitor is <br />on, and whether the inventory loss alarm has been activated. <br />