Laserfiche WebLink
`SWRCB,January 2002 Page 5 of 5 <br /> 8.FILL RISER CONTAINMENT SUMP TESTING <br /> Facility is Not Equipped With Fill Riser Containment Sumps ❑ <br /> Fill Riser Containment Sumps are Present,but were Not Tested ❑ <br /> Test Method Developed by ❑ Sump Manufacturer ® Industry Standard ❑ Professional Engineer <br /> ❑ Other(Specify) <br /> Test Method Used ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> ❑ Other(Specify) <br /> Test Equipment Used:Incon TS-STS Equipment Resolution: .0006 <br /> Fill Sump#Fill Fill Sump# Fill Sump# Fill Sump# <br /> #UE020U001 <br /> Sump Diameter: 40" <br /> Sump Depth: 46" <br /> Height from Tank Top to Top of N/A <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 17" <br /> Electrical Penetration: <br /> Condition of sump prior to testing: Good <br /> Portion of Sump Tested: 2"above Hi het Pent. <br /> Sump Material: Fiberglass <br /> Wait time between applying 30 Minutes <br /> pressure/vacuum/water and starting <br /> test: <br /> Test Start Time: 9:53 AM 10:08 AM <br /> Initial Reading Ri): 4.8414" 4.8407' <br /> Test End Time: 10:08 AM 10:23 AM <br /> Final Reading 4.8407' 4.8403" <br /> Test Duration: 15 MIN. 15 MIN. <br /> Change in Reading Rf-Ri : -.0007' -.0004" <br /> Pass/Fail Threshold or Criteria: .002 <br /> Test Result: N Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Is there a sensor in the sump? ® Yes ❑ No ❑ Yes ❑ No ❑ Yes ❑ No ❑ Yes ❑ No <br /> Does the sensor alarm when either ❑ Yes ® No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA <br /> product or water is detected? <br /> Was sensor removed for testing? ® Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA <br /> Was sensor properly replaced and LEI Yes N No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA <br /> verified functional after testing? <br /> Comments include any information on repairs made prior to testing,and recommended follow-up for failed tests <br /> Re-Installed Sensor To Lowest Point But Not Tested. <br />