Laserfiche WebLink
°SWRCB,January 2002 Page 4 of 5 <br /> 6.PIPING SUMP TESTING <br /> Test Method Developed by ❑ Sump Manufacturer ® Industry Standard ❑ Professional Engineer <br /> ❑ Other(Specify) <br /> Test Method Used ❑ Pressure D Vacuum ® Hydrostatic <br /> ❑ Other(Specify) <br /> Test Equipment Used: Incon TS-STS Equipment Resolution: .0006 <br /> Sump#Piping Sump# Sump# Sump# <br /> #UE020U001 <br /> Sump Diameter 40" <br /> Sump Depth 45" <br /> Sump Material Fiberglass <br /> Height from Tank Top to Top of 14" <br /> Highest Piping Penetration <br /> Height from Tank Top to Lowest 14" <br /> Electrical Penetration <br /> Condition of sump prior to testing Good <br /> Portion of Sump Tested(1) 2"above highest pipe pent. <br /> Does turbine shut down when <br /> sump sensor detects liquid(both ❑ Yes ❑ No SNA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No [INA D Yes ❑ No ❑ NA <br /> product and water)?* <br /> Turbine shutdown response time N/A <br /> Is sytem programmed for fail-safe D Yes ❑ No S NA ❑ Yes ❑ No ❑ NA D Yes D No ❑ NA ❑ Yes ❑ No ❑ NA <br /> shutdown?* <br /> Was fail-safe verified to be ❑ yes ❑ No SNA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No DNA <br /> operational?* <br /> Wait time between applying <br /> pressure/vacuum/water and starting 30 Min. <br /> test <br /> Test Start Time 11:31 AM 11:50AM <br /> Initial Reading Ri) 5.9875" 5.9877' <br /> Test End Time 11:46 AM 12:06 PM <br /> Final Reading R 5.9877' 5.9877' <br /> Test Duration 15 MIN. 15 MIN. <br /> Change in Reading Rf-Ri +.0002" .0000 <br /> Pass/Fail Threshold or Criteria .002 <br /> Test Result S Pass ❑ Fail D Pass D Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Was sensor removed for testing? S Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA <br /> Was sensor properly replaced and D Yes S No D NA ❑ Yes ❑ No ❑ NA D Yes D No ❑ NA ❑ Yes ❑ No D NA <br /> verified functional after testing? <br /> Comments include any information on repairs made prior to testing,and recommended follow-up for failed tests <br /> Re-Installed Sensor To Lowest Point But Not Tested. <br /> (1)If the entire depth of the sump is not tested,specify how much was tested.If the answer to any of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire sump must be tested.(See SWRCB LG-160) <br />