Laserfiche WebLink
SWRCB,January 2002 <br /> 8. FILL RISER CONTAINMENT SUMP TESTING <br /> Facility is Not Equipped With Fill Riser Containment Sums ❑ <br /> Fill Riser Containment Sumps are Present,but were Not Tested ❑ <br /> Test Method Developed By: ❑Sump Manufacturer X❑Industry Standard ❑Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑Pressure ❑Vacuum ®Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used: Incon TS-STS Equipment Resolution: .0006 <br /> UE0200001 <br /> Sump Diameter: 40" <br /> Sump Depth: 46" <br /> Height from Tank Top to Top of NA <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 17" <br /> Electrical Penetration: <br /> Condition of sump prior to Good <br /> testing: <br /> Portion of Sump Tested 2"above collar <br /> Sump Material: fiberglass <br /> Wait time between applying <br /> pressure/vacuum/water and 15min <br /> starting test: <br /> Test Start Time: 10:11 am 10:27am <br /> Initial Reading Ri): 5.0162 5.0162 <br /> Test End Time: 10:27am 10:42am <br /> Final Reading(RF): 5.0163 5.0163 <br /> Test Duration: 16min 115min <br /> Change in Reading (RF—RI): .0001 .0001 <br /> Pass/Fail Threshold or Criteria: .002 .002 <br /> Test Result. (91 Pass ❑Fail ❑ Pass ❑Fail ❑ Pass. ❑Fail ❑ Pass ❑Fail <br /> Is there a sensor in the sump? ®Yes ❑No ❑Yes ❑No ❑Yes ❑No ❑Yes ❑No <br /> Does the sensor alarm when ®NA <br /> either product or water is [:]Yes [ENo ❑yes❑No❑NA ❑Yes❑No❑NA ❑Yes❑No❑NA <br /> detected? <br /> Was sensor removed for testing? ®Yes ❑No [:]NA ❑Yes❑No❑NA ❑Yes❑No❑NA ❑Yes❑No E-1 NA <br /> Was sensor properly replaced and ❑Yes ®No ❑NA <br /> verified functional after testing? ❑Yes[—]No[:INA ❑Yes❑No❑NA ❑Yes❑No❑NA <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> Sensor was removed but not tested, reinstalled to lowest point. <br /> k k 'yF 4 <br /> H <br /> "" ,r cs s��I; R j;;I i�.���,F <br />