Laserfiche WebLink
Attachment 2 <br /> Summary of Performance Estimates <br /> Pipeline Leak Detection System <br /> Used as a <br /> Line Tightness Test <br /> Complete this page if the pipeline leak detection system has been evaluated as an hourly test. <br /> Please complete the first table. Completion of the last three tables is optional. (The last three tables <br /> present the performance of the system for different combinations of thresholds, probabilities of false <br /> alarm,and probabilities of detection. They are useful for comparing the performance of this system to <br /> that of other systems.) <br /> Performance of the Pipeline Leak Detection S stem as Evaluated <br /> Description = _Leak Rate PD PFA Threshold <br /> ( al/h) I I I (gal/h) <br /> Evaluated System 0.10 1.00 0 0.068 <br /> EPA Standard 1 0.10 0.95 0.05 N/A <br /> Probability of False Alarm as a Function of Threshold <br /> Threshold Probability of False Alarm <br /> (gal/h) <br /> Not determined Not determined <br /> Probabili of Detection as a Function of Threshold for a Leak Rate of 0.10 al/h <br /> Threshold Probability of Detection <br /> (gal/h) <br /> Not determined Not determined <br /> Smallest Leak Rate that Can be Detected with the Specified Probability of Detection <br /> and Probabili of False Alarm <br /> Leak Rate Probability of Detection Probability of False Alarm <br /> (gal/h) <br /> Not determined Not determined Not determined <br />