Laserfiche WebLink
The following is an itemized list of underground storage tank violations that have not <br /> been addressed for DINO MART as of January04, 2018. <br /> Open violations from March 09, 2017 inspection <br /> Violation#206-Failure to comply with UST operating permit conditions. <br /> The following was noted: <br /> 1)The diesel underground fiberglass fitting located adjacent to UDC 3/4 was replaced under permit number <br /> SR0072496, this repair was required to be reinspected/retested 6-month upon installation, however this testing was <br /> not conducted. Immediately schedule with EHD all required follow up testing in connection with this SR0072496 <br /> permit. <br /> 2)The Veeder Root system appears to have been upgraded in September 2016 and a permit was not obtained <br /> from the EHD. According to the designated operator inspection report dated 9-6-2016, the system is"missing alarm <br /> history due ISD upgrade". Emergency repairs relating to UST system monitoring and release detection may be <br /> performed by a properly licensed, trained, and certified contractor pursuant to the EHUS policy and a permit <br /> obtained within one business day from the EHD. All other repairs must have a permit submitted to and approved by <br /> the EHD prior to beginning work. Immediately obtain a permit from the EHD for this repair. A"Failure to Obtain a <br /> Permit' penalty applies. Submit proof of correction to the EHD. <br /> Open violations from January 29, 2016 inspection <br /> Violation#103-Current financial responsibility documents not submitted. <br /> Financial responsibility documents have not been submitted to the EHD; the submitted documents are dated <br /> 11-21-2014. Current financial responsibility documents are required to be submitted annually. Immediately log into <br /> the California Environmental Reporting System (CERS) at http://cers.calepa.ca.gov/, and upload the required <br /> documents. <br /> Violation#121 -Failed to submit a written response within 30 days of receiving an inspection report. <br /> An inspection was last done on 2-26-2015 and an inspection report was issued identifying information to be <br /> submitted to bring this site into compliance. This information was required to be submitted by 3-26-2015. Only <br /> partial return to compliance documentation was received, resulting in a non-compliant status for this facility. An <br /> operator that receives an inspection report shall have 30 days to submit a written response that includes a <br /> statement documenting corrective actions taken or proposing corrective actions which will be taken. Ensure that a <br /> written response documenting corrective actions taken or proposed is submitted within 30 days of receiving an <br /> inspection report. <br /> Violation#203 -Failed to maintain records of monitoring, repair, lining,and upgrades on site. <br /> Records of the most recent monitoring system certification and the secondary containment testing reports were not <br /> found on site. These records shall be kept on site for the life of the tank. Immediately locate and maintain these <br /> records on site and submit copies to the EHD. <br /> Violation#204-Current monitoring plan approved by the EHD not found on site. <br /> An approved copy of the monitoring plans were not available for inspection. A copy of these plans shall be <br /> accessible on site at all times. Immediately locate and retain a copy on site. <br /> Violation#209 -Designated operator did not inspect all required items and/or the inspection reports not <br /> completed. <br /> The designated operator failed to check and note the correct test dates for the secondary containment testing on all <br /> 2015 designated operator monthly inspection reports. According to the received secondary containment testing <br /> results, the secondary containment testing was conducted on 3-2-2015; the designated operator reports list it as <br /> 3-18-2015. During the monthly inspection, the designated operator shall check that all required testing and <br /> maintenance for the UST system have been completed and document the dates they were done. Ensure that <br /> designated operators performing monthly inspections at this facility are including all of the required information on <br /> the reports. <br /> Page 2 of 3 <br />