Laserfiche WebLink
ANNUAL TEST RESULTS FOR THE PRODUCT AND VAPOR OVERFILL CONTAINMENT <br />Name: Lawrence Livermore National Laboratory Date: 10-23-2003 <br />Address: Site 300, Tracy, CA 95376 Bldg: 879 <br />Test Method Developed By: ❑ Spill Bucket Manufacturer 0 Industry Standard ❑ Professional Engineer <br />❑ Other (Specify) <br />Test Method Used: 1M Hydrostatic <br />❑ Other (Specify) <br />Test Equipment Used: Visual Inspection Equipment Resolution: <br />NA <br />Spill Box # <br />Spill Box # <br />Spill Box # <br />Spill Box # <br />879-DlU1 <br />879-G3U1 <br />Nominal Bucket Capacity in 5 gallons <br />5 gallons <br />gallons: <br />Test fails if the bucket does NA <br />NA <br />not hold at least 5 gallons <br />Bucket Depth (inside 18.0" <br />15.0" <br />measurement): <br />Wait time between filling with 5 minutes <br />5 minutes <br />water and starting test: <br />Test Start Time: 1:15p <br />1:10P <br />Initial Reading (Ri): 8.75" <br />11.50" <br />Test End Time: 2:15p <br />2:10p <br />Final Reading (RF): 8.75" <br />11.50" <br />Test Duration: 60 minutes <br />60 minutes <br />Change in Reading (Fr&): 0.00" <br />0.001, <br />Pass/Fail Threshold / Criteria: 0.00" <br />0.00" <br />Test Result: ® Pass ❑ Fail <br />® Pass ❑ Fail <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />Test water was disposed of in customers oil / water separator. <br />