Laserfiche WebLink
SWRCB,January 2002 Page 3 of 3 <br /> 7. ER-DISPENSER CONTAINMENT UD TESTING <br /> Test Method Developed By: 0 UDC Manufacturer N Industry Standard 0 Professional Engineer <br /> 0 Other(Specify) <br /> Test Method Used: 0 Pressure 0 Vacuum N Hydrostatic <br /> 0 Other(Spec6) <br /> Test Equipment Used:Incon Sump Tester Equipment Resolution:.002 <br /> UDC#7!8 UDC# UDC!# UDC# <br /> UDC Manufacturer: Bravo <br /> UDC Material: Meta <br /> UDC D the 9t1 <br /> Height from UDC Bottom to Top Bottom of UDC <br /> of Highest Pi2ing Penetration: <br /> Height from UDC Bottom to Bottom of UDC <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to <br /> testin : OK <br /> Portion of UDC Tested 611 <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both 0 Yes 0 No �9 NA 0 Yes 0 No 0 NA 0 Yes 0 No 0 NA 0 Yes ❑No 0 NA <br /> product and water)?* <br /> Turbine shutdown response time WA <br /> Is system programmed for fail- 0 Yes 0 No X NA ❑Yes 0 No 0 NA 0 Yes 0 No 0 NA 0 Yes 0 No 0 NA <br /> safe shutdown?` <br /> Was fail-safe verified to be 0 Yes ❑No 9WA 0 Yes 0 No 0 NA 0 Yes 0 No 0 NA 0 Yes 0 No [INA <br /> o erationalf <br /> Wait time between applying <br /> pressure/vacuum/water and 15 min <br /> starting test <br /> Test Start Time: 12:18 pm <br /> Initial Readin j : 0.1142 <br /> Test End Time: 12:34 pm <br /> Final Reading 0.1128 <br /> Test Duration: 15 min <br /> Change in Reading (RF-RJ: 0.0014 <br /> Pass/Fail Threshold or Criteria: .002 <br /> Test Result: 19 Pass ❑Fall ❑ Pass ❑Fall ❑ Pass ❑Fail ❑ Pass ❑Fail <br /> Was sensor removed for testing? 0 Yes 0 No RNA ❑Yes []No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No 0 NA <br /> Was sensor properly replaced and 0 Yes ❑No 9 NA 0 Yes ❑No 0 NA ❑Yes 0 No ❑NA 0 Yes 0 No ❑NA <br /> verified functional after testin ? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> 1 If the entire depth of the UDC is not tested,specify how much was tested. If the answer to Any of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br />