7. UNDER-DISPENSER CONTAINMENT DC TESTING <br /> Test Method Developed By: ❑ UDC Manufacturer ® Industry Standard ❑Professional Engineer <br /> ❑ Other(Spec) <br /> Test Method Used: ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> ❑ Other(Spec) <br /> Test Equipment Used: INCON SUMP TESTER Equipment Resolution: +/-0.002" <br /> UDC#1-2 UDC#3-4 UDC#5-6 UDC#7-8 <br /> UDC Manufacturer: BRAVO PAN BRAVO PAN BRAVO PAN BRAVO PAN <br /> UDC Material: STEEL STEEL STEEL STEEL <br /> UDC Depth: 12" 12" 12" 12" <br /> Height from UDC Bottom to Top N/A N/A N/A N/A <br /> of Highest Piping Penetration: <br /> Height from UDC Bottom to N/A NIA N/A N/A <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to DRY DRY DRY DRY <br /> testing: <br /> Portion of UDC Tested ABOVE ABOVE ABOVE ABOVE <br /> PENETRATIONS PENETRATIONS PENETRATIONS PENETRATIONS <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both ❑Yes ❑No ®NA ❑Yes ❑No ®NA ❑Yes ❑No ®NA ❑Yes ❑No ®NA <br /> product and water)?` <br /> Turbine shutdown response time N/A N/A N/A NIA <br /> Is system programmed for fail- []Yes ❑No ®NA ❑Yes ❑No ®NA []Yes ❑No ®NA ❑Yes ❑No ®NA <br /> safe shutdown?` <br /> Was fail-safe verified to be ❑Yes ❑No ®NA ❑Yes ❑No ®NA ❑Yes ❑No ®NA ❑Yes ❑No ®NA <br /> operational?* <br /> Wait time between applying <br /> pressure/vacuum/water and 10 MIN 10 MIN 10 MIN 10 MIN <br /> starting test <br /> Test Start Time: 8:45 AM 8:45 AM 8:04 AM 8:04 AM <br /> Initial Reading(RI): 1.2391" 2.8623" 2.9857" 2.8421" <br /> Test End Time: 9:00 AM 9:00 AM 8:19 AM 8:19 AM <br /> Final Reading(RF): 1.2407" 2.8622" 2.9855" 2.7963" <br /> Test Duration: 15 MIN 15 MIN 15 MIN 15 MIN <br /> Change in Reading(RF-RI): 0.0016" -0.00011, -0.0002" -0.0458" <br /> Pass/Fail Threshold or Criteria: +/-0.002" +/-0.002" +/-0.002" +/-0.002" <br /> Test Result: ®Pass ❑ Fail Z Pass ❑ Fail N Pass El Fail ❑Pass Z-Fail <br /> Was sensor removed for testing? ❑Yes [:]No ®NA [:]Yes ❑No ®NA ❑Yes []No ®NA ❑Yes ❑No ®NA <br /> Was sensor properly replaced and <br /> verified functional after testing? ❑Yes []No ®NA ❑Yes ❑No ®NA ❑Yes [:]No ®NA El Yes F1 No ®NA <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> ABOVE IS THE LAST OF TWO BACK TO BACK 15 MINUTE TESTS <br /> ALL UDC'S ABOVE HAVE FLOAT&CHAINS AS SECONDARY LEAK DETECTORS <br /> ALL FLOAT&CHAINS WORK PER MANUFACTURES SPECS. <br /> 'If the entire depth of the UDC is not tested, specify how much was tested. If the answer to Any of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br />