Laserfiche WebLink
FILE COPY <br /> 1777 W Yosemite Ave, Manteca, CA SR0067724 <br /> 4. Sheet number FO-M1.2, Modified Above Ground Fueling Piping Plan (Generator F.O.S/ <br /> F.O.R Pipe modification @ Boiler Room), illustrates a return line from the boiler (E) <br /> F.O.R FROM (E) BOILER becoming (E) F.O.R FROM (AST). Submit a revised sheet <br /> number FO-M1 with the required information. <br /> 5. Since the existing Owens Corning/PU sensors can not be used with the existing Veeder <br /> Root TLS-350 Plus monitoring panel, submit sensor specifications for the proposed <br /> sensors that are compatible with the Veeder Root monitoring panel, revise Page 3 of the <br /> UST System Retrofit or Repair Form and submit for the EHD review and approval. <br /> If you have any further questions, please don't hesitate to contact me at (209) 953-7699. <br /> Sincerely, <br /> .rOrz. <br /> Elena K. Manzo, EHS <br /> Environmental Health Specialist <br /> CC: Tonia Shaw, HEM <br /> 1777 W Yosemite Ave, <br /> Manteca, CA 95357 <br />