Laserfiche WebLink
*TANK ANNULAR TESTING is <br />Test Method Developed By: 0 Tank Manufacturer 0 Industry Standard 0 Professional Engineer <br />El Other (Specify) <br />Test Method Used: 0 Pressure 0 Vacuum F-1 Hydrostatic <br />El Other (Specify) <br />Test Equipment Used: Test plugs, venturi pump and gauges <br />Equipment Resolution: 0.5% of span <br />Diesel <br />Is Tank Exempt From Testing?' <br />No <br />Tank Capacity: <br />10,000 <br />Tank Material:Fiberglassvtle; <br />I <br />Tank Manufacturer: <br />Owens Corning <br />Product Stored: <br />D <br />FEB 02 zol <br />Wait time between applying <br />pressure/vacuum/water and <br />�n test: <br />10 minutes <br />ENVIRONMENTAi <br />Test Start Time: <br />10:00 AM <br />Initial Reading (Ri): <br />10 In. Vac <br />Test End Time: <br />11:00 AM <br />Final Reading (RF): <br />10 In. Vac <br />Test Duration: <br />60 Min <br />Change in Reading (R,,-R,): <br />0 In. Vac <br />Pass/Fail Threshold or Criteria: <br />No Detectable Loss <br />Test Result: <br />Pass <br />Was sensor removed for testing? <br />Yes <br />Was sensor properly replaced and <br />verified functional after te <br />Yes <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />1 Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br />containment such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment <br />testing. {California Code of Regulations, Title 23, Section 2637(a)(6)) <br />