Laserfiche WebLink
6. PIPING SUMP TESTING <br />Test Method Developed By: ❑ Sump Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Specify) <br />Test Method Used: ❑ Pressure ❑ Vacuum ® Hydrostatic <br />❑ Other (Specify) <br />Test Equipment Used: Incon Sump Tester <br />Equipment Resolution: +/- 0.002" <br />Sump # Diesel <br />Sump # <br />Sump # <br />Sump # <br />Sump Diameter: 42+1 <br />Sump Depth: 60" <br />Sump Material: Fiberglass <br />Height from Tank Top to Top of 2411 <br />Highest Piping Penetration: <br />Height from Tank Top to Lowest „ <br />Electrical Penetration: 27 <br />Condition of sump prior to testing: Good <br />Portion of Sump Tested' 2" Above Pen. <br />Does turbine shut down when <br />sump sensor detects liquid (both ❑ Yes ❑ No U NA <br />product and water)?* <br />❑ Yes ❑ No ®NA <br />❑ Yes ❑ No ®NA <br />❑ Yes ❑ No ®NA <br />Turbine shutdown response time N/A <br />Is system programmed for fail-safe ❑ yes ❑ No ®NA <br />shutdown? <br />❑ Yes ❑ No ®NA <br />❑ Yes ❑ No ®NA <br />❑ Yes ❑ No ®NA <br />Was fail-safe verified to be ❑ yes ❑ No ®NA <br />o erational?+ <br />❑ Yes ❑ No ®NA <br />❑ Yes ❑ No ®NA <br />❑ Yes ❑ No ®NA <br />Wait time between applying <br />pressure/vacuum/water and starting 30 minutes <br />test: <br />Test Start Time: 11:44 AM 12:02 PM <br />Initial Reading (RI): 4.7661 4.6898 <br />Test End Time: 11:59 AM 12:17 PM <br />Final Reading (RF): 4.7016 4.6454 <br />Test Duration: 15 min. 15 min. <br />Change in Reading (RF -RI): -0.0645 -0.0444 <br />Pass/Fail Threshold or Criteria: +/-0.002" <br />Test Result: Fail <br />Was sensor removed for testing? Yes <br />Was sensor properly replaced and Yes <br />verified functional after testing? <br />Comments — (include information on repairs made prior to testing, and recommended follow-ttp for failed tests) <br />Sensor functionality was not confirmed. This procedure is not part of the Secondary Containment Testine scope of work. <br />' If the entire depth of the sump is not tested, specify how much was tested. If the answer to any of the questions indicated with an <br />asterisk(*) is "NO" or "NA", the entire sump must be tested. (See SWRCB LG -160) <br />