Laserfiche WebLink
0 <br /> Page 9 of 9 <br /> 9. SPILL/OVERFILL CONTAINMENT BOXES <br /> Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ <br /> Spill/Overfill Containment Boxes are Present,but were Not Tested ❑ <br /> Test Method Developed By: ❑ Spill Bucket Manufacturer Industry Standard ❑Professional Engineer <br /> Q Other(Spec) <br /> Test Method Used: ❑Pressure ❑Vacuum ®Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: See attached testing procedures Equipment Resolution: <br /> Spill Box#87-1 vapor Spill Box#87-2 vapor Spill Box#91 vapor Spill Box# <br /> Bucket Diameter&Brand: 12"Philtite 12"Philtite 12"Philtite <br /> Bucket Depth: 15" 14.5" 14.5" <br /> Wait time between applying <br /> pressure/vacuum/water and 30 Minutes 30 Minutes 30 Minutes <br /> starting test: <br /> Test Start Time: 11:05am 11:01am 11:01am <br /> Initial Reading(Rj): 110.8569 0.7018 0.0912 <br /> Test End Time: 11:20am 11:16am 11:16am <br /> Final Reading(RF): 0.8566 0.7017 0.0915 <br /> Test Duration: 15 minutes 15 minutes 15 minutes <br /> Change in Reading(RF-RT): 0.00029 0.00003 0.00024 <br /> Pass/Fail Threshold or 0.002 0.002 0.002 0.002 <br /> Criteria: <br /> k 1. � � <br /> xF Q <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />