Laserfiche WebLink
The following is an itemized list of underground storage tank violations that have not <br /> been addressed for GAS DEPOT #2 as of May 06, 2017. <br /> Open violations from December 29, 2016 inspection <br /> Violation#201 -Failed to maintain alarm logs and/or records of follow up actions. <br /> Maintenance and monitoring records for the last three years were not found on site. The site is not maintaining <br /> alarm logs or maintenance logs for alarms addressed by the site without a technician. The alarms include: <br /> L1 (UDC 1/2) 1/5/16 Setup Data Warning <br /> L11 (91 fill) 1/18/16 Fuel Alarm <br /> L11 (91 fill) 3/22/16 Fuel Alarm <br /> L12 (87 STP) 1/5/16 Liquid Warning <br /> According to Mr. Hur, he tried responding to the 1/5/16 alarm, but did not know how to determine which sensor was <br /> having a problem or how to silence the alarm. He stated that in trying to silence the alarm on the monitoring panel, <br /> he caused a set up data warning on the UDC 1/2 sensor. Work orders were found on site for a technician resetting <br /> the Setup Data Warning for UDC 1/2. Mr. Hur stated that for all three liquid alarms, he pumped the liquid from the <br /> sump into a waste drum kept behind the store. No records were available for these responses. <br /> These records shall be maintained on site for at least three years. Monitoring records include: (1) date and time of <br /> all monitoring or sampling; (2) monitoring equipment calibration and maintenance records; (3) results of any visual <br /> observations; (4) results of sample analysis performed a lab or in the field; (5) logs of all readings of gauges or other <br /> monitoring equipment, ground water elevations, or other test results; (6) results of inventory readings and <br /> reconciliations. Immediately locate and maintain all maintenance and monitoring records for the last three years on <br /> site and submit copies to the EHD. <br /> Violation#204-Current monitoring plan approved by the EHD not found on site. <br /> An approved copy of the monitoring plans were not available for inspection. All copies of the monitoring plan on site <br /> were many years old and were outdated. A copy of these plans shall be accessible on site at all times. Immediately <br /> locate and retain a copy on site. <br /> Violation#205 -Failure to have an approved UST response plan available onsite. <br /> An approved copy of the response plan was not available for inspection. A copy of this plan shall be accessible on <br /> site at all times. Immediately locate and retain a copy on site. <br /> Violation #314-Failed to have secondary containment or secondary containment not tight. <br /> According to a phone call from Kim with Elite IV on January 30, 2015, three UDCs failed secondary containment <br /> testing on January 29, 2015 and permits were required for repairs. No permits were obtained for UDC repairs and <br /> no work orders were found on site for UDC repairs. All secondary containment for the UST system must be tight. <br /> Immediately have a properly licensed, trained, and certified contractor repair or replace the failed component under <br /> permit and inspection of the EHD. <br /> Open violations from December 30, 2015 inspection <br /> Violation#110-Failed to submit secondary containment test report within 30 days. <br /> Secondary containment testing was scheduled to be performed on 1-29-1015 and a test report has not been <br /> submitted to the EHD. A copy of the test report must be submitted within 30 days of the test. Immediately submit a <br /> copy of the test report to the EHD or schedule this test and provide 48 hours notification to the EHD. <br /> Violation#115-Failed to inform the EHD of a change of designated operator within 30 days. <br /> According to Mr. Hur, a new designated operator was hired sometime in November 2015 and a notification was not <br /> provided to the EHD within 30 days of the change. Any changes shall be reported to the EHD within 30 days. <br /> Immediately log into the California Environmental Reporting System (CERS) at http://cers.calepa.ca.gov and upload <br /> the notification identifying all the designated operators for this facility. <br /> Violation#204-Current monitoring plan approved by the EHD not found on site. <br /> An approved copy of the monitoring plans were not available for inspection. A copy of these plans shall be <br /> accessible on site at all times. Immediately locate and retain a copy on site. <br /> Page 2 of 3 <br />