Laserfiche WebLink
Scismic/Anchoring: <br />Tank anchorage is specifically designed for linear and crosslinked polyethylene tanks, and <br />consists of bolts or metal clips anchored to the concrete foundation pad, with cables running <br />between the clip and hold downs on the top of the tank These are designed by a civil/structural <br />engineering firm, and are purchased from the tank manufacturer, Snyder Industries or Poly <br />Processing Co. The system for the wastewater cone bottom tank is shown in the attached signed <br />and stamped drawings. <br />Seismic/Anchoring findings: The tanks as designed and operated, and the containment areas in which <br />they are located, are adequately anchored and are seismically sound. <br />Initials: <br />Leak `('est: <br />A leak test was conducted by filling the tanks with wastewater and inspecting for leaks. There <br />were no signs of leakage. <br />Tank Integrity_ .Based on the fact that the tanks are new (purchased in 2016) and have contained <br />waswwatcr without signs of leakage, the tanks have sufficient integrity for their intended use. <br />Initials -k"7 <br />Tank Drawing: <br />1IIASa�-1�4t�L <br />(A <br />Facing <br />N E S W <br />Tank Uiameters: 11 ft 10 in, 4 ft and 4 ft <br />Tank height: 15 ft 3 in, 5 ft 7 in and 4 ft <br />Tank Gross Capacity 8285 gallons <br />California Tank Lines, Inc. Wastewater Processing Tanks (3) <br />