Laserfiche WebLink
Seismic/Anchoring: <br />Tank anchorage is specifically designed for linear and crosslinked polyethylene <br />tanks, and consists of bolts or metal clips anchored to the concrete foundation <br />pad, with cables running between the chp and hold downs on the top of the tank. <br />These are designed by a civillstructural engineering film, and are purchased from <br />the tank manufacturer, Poly Processing Co. <br />Seismic/Anchoring findings: The tanks as designed and operated, and the containment <br />areas in wtuch they are located, are adequately anchored and are seismically sound. <br />lnitials:W, 7 <br />Leak Test: <br />A leak test was conducted by filling the tank with wastewater and inspecting for <br />leaks. There were no signs of leakage. <br />Tank Integrity: Based on the fact that the tanks have contained wastewater without ­ <br />signs of leakage, and inspection shows no signs of cracking or corrosion, the tanks have <br />sufficient integrity for their intended use. <br />Initials: <br />Tank Drawing: <br />¢ IV u? vPizerr <br />Facing <br />NF,S W <br />Tank Diameters: 4 ft <br />Tank Height: 4 ft <br />Tank Gross Capacity: 1110 gallons <br />California Tank Lines, Inc. Final Neutralizer Tanks (3) <br />