Laserfiche WebLink
Secondary Containment Assessment Page B: <br />Owrhaad view: <br />OD <br />I8/ <br />Cross sectional (luelal) view. <br />Volume calculations: <br />Tank volume (largest tank): 370 gallons. <br />Containment volume 6W gallons (gross) <br />Less tank volume = 140 gallons, containment volume = 500 gallons (net) <br />Area is covered, protected from sun and rain_ <br />Therefore, secondary containment volume is adequate. <br />Design of containment area: Secondary containment is provided by a 6 in. high curb <br />around the concrete slab. The containment area does not have cracks or gaps to allow the <br />escape of spilled materia]. The containment area is coated with an epoxy which is re- <br />applied annually, and is cquippexd with a level indicator for leak detection which will <br />sound an alarm when liquid is detected. Liquid is recycled using an AODD pump_ <br />Site Security: The entire site is fenced. The gate is locked when company personnel are <br />not present- <br />Secondary <br />r sent <br />Secondary Containment findings: The secondary containment system is of sufficient <br />capacity and condition for the containment of releases from the 370 gallon neutralizer <br />tanks and ancillary equipment. Initials: <br />California Tank Lines, inc_ Final Neutralizer Tanks (3) <br />