Laserfiche WebLink
UNDERGROUND STORAGE TANK REMOVAL <br /> AT&T <br /> MICROWAVE RELAY FACILITY <br /> LODI,CALIFORNIA <br /> PPM A soil sample collected from the sail imported to backfill the excavation had no detected <br /> concentrations of TPH-D or VOCs Metals concentrations detected in the backfill soil sample had <br /> concentrations below total threshold hmit concentrations established in the California Code of <br /> Regulations (Title 22, Division 4 5, Chapter 11, Article 3) and do not qualify the soil as a <br /> hazardous waste <br /> TABLE 5-1. Organic Analytical Results of Soil Samples Collected at AT&T, Microwave Relay Facility, <br /> Lodi, California, on March 4, 1999 <br /> Sample No Sample TPH-D Benzene Toluene Ethyl- Total MTBE VOCs <br /> Depth (ppm) (Ppm) (Ppm) benzene Xylenes (ppm) (ppm) <br /> (feet) (Ppm) (Ppm) <br /> ATT-S-16' 16 4,900 ND ND ND ND ND -- <br /> ATT-SW-15' 15 3,800 ND ND ND ND ND -- <br /> ATT-NW-13 5' 13 5 660 ND ND ND ND ND -- <br /> ATT-N-16' 16 22 ND ND ND ND ND <br /> ATT-E-115' 115 360 ND ND ND ND ND -- <br /> ATT-PIPING-3 5' 3 5 1 8 ND ND ND ND ND -- <br /> ATT-SP-1,2,3 Surface 2,800 ND ND ND ND ND -- <br /> (COMP) <br /> ATT-SP-4 Surface 340 ND ND ND 013 ND -- <br /> (COMP) <br /> ATT-SP-5,6,7 Surface 82 ND ND ND ND ND -- <br /> (COMP) <br /> BACKFILL 1 Surface ND -- -- -- -- -- ND <br /> Reporting Limits -- 1 to 100 0 0050 00050 :00:07077 <br /> 00050 0 025 Various <br /> TPH-D total petroleum hydrocarbon as diesel fuel <br /> ND not detected at or above the laboratory reporting lima <br /> ppm palls per million(mg/Kg) <br /> — not analyzed/not applicable <br /> ATC Associates Inc - _ 61059 0029 <br /> 5 <br />