Laserfiche WebLink
20200037 <br /> e a <br /> s e: <br /> u�¢at�a <br /> Line Leak Detector Test Data Sheet <br /> Station # Arco 6080 Date .January 21ST 2020 <br /> Address 85 E Louise <br /> Lathrop, CA 95330 <br /> Test Information <br /> 1 2 3 4 5 <br /> Product 87 9i <br /> DSL <br /> Manufacturer VR VR VR <br /> Model 89848,, 848480 848480 <br /> Full Operating Pressure(psi) 36 34 32 <br /> Line Bleed Back(ml) NA NA NA <br /> Trip Time(sec) NA NA NA <br /> Metering Pressure(psi) NA NA NA <br /> F/E Holding Pressure(psi) <br /> 21 21 22 <br /> Test Leak Rate (ml,min)(gpli) 189ML 18914L 189ML <br /> PASS or FAIL PASS PASS PASS <br /> Comments: <br /> This letter certifies that the annual leak detector testy were perlonned at the abo%c referenced l"Icility <br /> according to the equipment manufacturers procedures and limitations and the results as listed are to my <br /> knowledge true and correct_ The mechanical leaf: test detector test pass.fail is determined using a low <br /> flow threshold trip rate of 3 gpli at 10 PSI. <br /> Inspected By: Contractor Gettler-Ryan Inc. <br /> Technician Matthew Campbell Lic#220793 <br /> Signature 71 W- /,,z, fir/ <br />